Tests were performed in the test area of Harju Elekter Elektrotehnika, Keila Estonia. HECON LIGHT switchgear (Figure 33 – Figure 36) was used for the testing. The technical specifications of the switchgear are presented in Table 2.

Type HECON

Degree of protection enclosure IP44

Earthing system TN-S

Main busbars (L1, L2, L3) 2 × 30 × 10 Al

Main busbars (PE) 1 × 30 × 10 Al

Enclosure dimensions H × W × D [mm] 2100 + 100 × 750 × 265

Table 2. Technical specifications of HECON LIGHT test switchgear (Appendixt 4 & 5)

The main devices in the switchgear concerning the tests were the main switch, busbars and the outgoing MCCB. There were other devices in the switchgear, but those did not participate in the tests and are therefore not presented in this thesis.

46

Figure 34. View of HECON test switchgear with doors open

Figure 33. View of HECON test switchgear with doors closed

Figure 36. MCCB 250 A in the HECON test switchgear, Siemens 3VA1225-4EF32

Figure 35. Main switch in the HECON test switchgear, Socomec Sirco 630 A

47 3.2 Testing method

The tests were performed with two different scenarios (test 1 and test 2). In both scenarios, the temperatures of the main switch’s incoming and outcoming connections were measured. IS type sensors were used for measuring the connection points of the main switch. The sensors were attached on the supply cable insulation as close as possible to the connection point. IS type sensors were installed under the bolts of the outgoing busbars of the main switch. The differences between the tests were that in the test 1 the main switch (MS) and the busbars were tested with the rated current (630 A). In the test 2 additional sensors were attached to the load side phase cables of the outgoing MCCB and sensors from the main busbars were reinstalled to the supply cables of the MCCB that were connected with the busbars. Then MCCB was loaded with the rated current of the MCCB (250 A) with load resistors.

In both tests, temperatures were analysed with three different monitoring systems. The IntelliSAW system, which was the system under testing and verification, was the main system.

The second system was Harju Elekter’s self-assembled temperature monitoring system with wired sensors. The wired sensors were installed in the same locations, where the wireless IntelliSAW sensors were installed. The third system was thermal imaging. Thermal images were taken at the end of each test from the same locations, where wired and wireless sensors were installed. The results from all the three monitoring systems were compared after the tests.

The wired sensor system was built from the following devices:

1. Thermocouples Z2-K-5M, Farnell 2. Amplifiers AD8495, Analog devices

3. PicoLog 1012 Data Logger and PP604 Terminal Board

Thermal camera that was used in the tests was Fluke Ti400.

48 Prior to the testing the expected busbar temperatures were evaluated. The busbars in the HECON test switchgear were sized according to the rated current of the switchgear, doubled 30 x 10 aluminium (for currents up to 780 A in free air, according to reference ABB. 2000).

The temperature rise of the busbars was designed 30 K. The ambient temperature according to the standard IEC 61439-1 must be considered 35 celsius degrees. The expected end busbar temperature would be 65 celsius degrees at the ambient temperature of 35 celsius degrees. The load current in the test 1 was 630 A, which is lower than 780 A, and the ambient temperature in the tests was appr. 22 not 35 celsius degrees, so the first expectations were that the busbar temperatures could be lower than 65 celsius degrees. However, in the tests all the air ventilations were blocked to meet the general IP44 protection degree for the switchgear. When natural air ventilation is not considered in the switchgear, the air temperature inside the switchgear should be higher, thus the busbars heat up more and the busbar temperatures would be higher than in free air. (ABB. 2000)

When both tests were performed, similar results from each temperature monitoring system were expected. Should the results be similar, it could be stated that the installation and configuration of the IntelliSAW system was successful and the system is working correctly and the data received is reliable. Should these three monitoring systems give all different data, further testing and analysis must be done, which of these three monitoring methods is accurate.

In both tests (test 1 and test 2), sensors were installed to monitor the main switch’s incoming and outgoing connections (Figure 37).

49

Figure 37. Sensors installed on the connection points of the main switch

The HECON test switchgear was powered by Harju Elekter’s own supply cabinet. The supply cabinet is designed to carry out different temperature rise tests. The supply cabinet consists of a three-phase 17 kVA main transformer, which primary side can be supplied from the grid (400 VAC). The voltage of the secondary side of the voltage transformer is very low, only 3 x 1,5-3,5 VAC, but this enables high output current up to 4000 A (Figure 38).

Figure 38. Main transformer of the supply cabinet

The supply cabinet contains an adjustable autotransformer per each phase, where the primary voltage of the main transformer can be adjusted. With the autotransformers it is possible to adjust the output current of the supply cabinet. In the testing area, it is possible to test different switchgears either by short-circuiting the test switchgear’s main busbars with a copper busbar to load the switchgear without any loads (with the autotransformers it is possible to adjust the

50

“short-circuit current” to the rated current of the switchgear) or by loading outgoing circuits with loading resistors. The HECON test switchgear main busbars were short circuited (Figure 43) in the test 1 to load the switchgear with rated current of 630 A. Autotransformers can be seen in the Figure 39 just above the cable connection. The meters above the autotransformers display values of voltages and currents in the grid side.

Figure. 39 Supply cabinet

3.3 Software setup

Prior testing the auxiliary components of both monitoring systems were placed outside of the test switchgear. Author and the electrical engineer from As Harju Elekter Elektrotehnika supporting these tests were both analysing data throughout the testing. Figure 40 presents the test environment, where were two laptops, one for the wired system and one for the wireless Intellisaw system. Author was operating with the IntelliSAW system data.

.

Figure 40. Test environment, data analysing

51 IntelliSAW system configuration was done successfully according to the manufacturer’s manual (Intellisaw 2016. IntelliSAW IntelliSAW Configuration Tool User Manual). Each sensor was found by the system and temperatures were corresponding to the ambient temperatures. Sensors were named by the locations, where those were installed (Figure 41).

Figure 41. Sensor data in temp sensor display before tests.

52 3.4 Test 1

In the test 1 the HECON test switchgear main busbars were short circuited (Figure 43) to load the switchgear with the rated current of 630 A. Figure 42 presents the principle diagram of the test 1. The same figure can be found from the appendices, Appendix 8.

Figure 42 Principle diagram of test 1

The HECON test switchgear had been designed in a way that it was easy and safe to short circuit the busbars. Figure 43 presents the short circuit bar that was used to connect the main busbars together.

Figure 43. Short circuit busbar

53 Figure 44 presents the installation of busbar sensors.

Figure 44. Test 1 register 424-426 sensors

In test 1 sensors were installed as shown in figures 37 and 44. In this test the outgoing MCCB feeder was not analysed and excessive sensors of registers 427 – 429 were used to measure the cable connections of the supply cabinet. One sensor was placed to measure the ambient temperature and the two sensors were installed to measure the phases of L1 and L2 of the cable connections of the supply cabinet (Figure 45).

Figure 45. Test 1 register 427-429 sensors

54 3.5 Test 2

In test 2 the outgoing MCCB feeder was loaded with rated current and the temperatures of the cable connections of the MCCB were measured. Figure 46 presents the principle diagram of test 2. The same figure can be found from the appendices, Appendix 9.

Figure 46. Principle diagram of test 2

In this test, the MCCB was loaded with load resistors and the short circuit busbar was not used.

The sensors presented in Figure 47 were installed to the outgoing cable connections of the outgoing MCCB.

Figure 47. Test 2 register 427-429 sensors

55 Sensors that were installed to the busbars in test 1 were re-installed to the cable connections of the cables between busbars and outgoing MCCB (Figure 48).

Figure 48. Test 2 register 424-426 sensors

In test 2 loading resistors were used (Figure 49). In the trolley there were four three-phase step-up transformers (that the currents in the loading resistors would be smaller compared with the currents in the switchgear) and three adjustable load resistors per each phase of the step-up transformer. In test 2, only one step-up transformer was needed to load the MCCB.

Figure 49. Loading resistors in test 2

56 Step-up transformer for the loading resistors had primary side voltage of 1.5 V and current 504 A and secondary side voltage of 400 V and current 1.9 A (Figure 50). The loading resistors for each phase were 165 ohms and 2 A (Figure 51).

Both the supply cabinet voltage and the resistance of load resistors were adjusted until the load in the MCCB circuit (Figure 52) was the same as the rated current of the MCCB 250 A.

Figure 52. Load current in the testing of the MCCB Figure 50. Step-up transformer Figure 51. Loading resistor

57 3.6 Test 1 results

Test 1 lasted three hours and 37 minutes. At first, 690 A load current was applied to speed up the temperature rise. When the temperatures had risen, the load current was set to the rated value of test HECON switchgear (630 A). In test 1, the main switch L1 wired sensor became loose after 50 minutes of testing. This can be seen in the test-1-wired-sensor report. Results are presented in Figure 53 (Appendix 8)

.

Figure 53. Temperature rise graph of test 1 with wired sensors

IntelliSAW software was recording data to an Excel file during the tests. One row of temperature data was recorded in every second. Total of 13334 rows of temperature data was created to the Excel file when test 1 was completed. Figure 54 is presenting the graph from the received Excel data. The results are also presented in attachments, Appendix 10.

58

Figure 54. Temperature rise graph of test 1 with IntelliSAW wireless sensors

In Table 3 are presented the steady state temperature values of the two temperature monitoring systems at the end of test 1. The first column indicates the measurement location. The second and the third columns present the steady state values of the wired sensor system and the wireless IntelliSAW sensor system. The differences between the results of the wired and IntelliSAW monitoring systems are brought out in the “Difference” columns (differences brought out in temperature K values and in percentage).

The temperature values of the main busbar are meeting the prior expectations described in chapter 3.2. In Table 2 the main busbar steady temperature is approximately 65 celsius degrees at the ambient temperature of 20 celsius degrees. Due to the blocked natural ventilation the main busbar temperature is higher than in the free air. This means that in the given circumstances the main busbars at 630 A rated current and in IP44 switchgear the steady state temperature would be 80 celsius degrees at the ambient temperature of 35 celsius degrees according to the standard IEC 61439-1. In comparison, in the free air the same busbars would reach steady state temperature of 65 celsius degrees at the ambient temperature of 35 celsius degrees and with current of 780 A.

59

Table 3. Comparison of results of test 1

At the end of the measurements, thermal images at the sensor locations were taken. Figures 55 – 62 illustrate the locations and the thermal images of each sensor location at the end of test 1. In the busbar images (Figure 57 & Figure 59) the temperature data of thermal imaging is also added to the photos of the locations. The reason for this is following. If for example Figures 57 and 59 are looked, it can be seen that in that the thermal imaging at location of the wired sensors are indicating temperature of ~40 degrees of celsius and the thermal imaging at the location of wireless sensors are indicating temperature of ~ 50 degrees of celsius.

However, if data in Table 2 is looked, it can be seen that both temperature monitoring systems are giving temperature results between 90 and 100 degrees of celsius. This is a big difference in temperatures between the thermal camera images and the sensors. As two separate monitoring systems are both registering values close to each other it can be concluded that the thermal imaging results are in this case not reliable.

Answer can be found in the IR imaging. Temperatures between 90 -100 degrees of celsius really exist in these connections, but those were not noticed straight away from the sensor locations.

This why it is important to read the thermal images correctly. If only direct locations of sensors are analysed the temperatures could be wrongly interpreted.

60

Figure 58. Busbar (BB) connection after main-switch (MS) L1, L2 and L3 IR image

Figure 55. Cable before MS L2 and L3 normal image

Figure 57. Busbar (BB) connection after main-switch (MS) L1, L2 and L3 normal image

Figure 56. Cable before MS L2 and L3 IR image

Figure 60. Horizontal and vertical BB connection L1, L2 and L3 IR image

Figure 59. Horizontal and vertical BB connection L1, L2 and L3 normal image

61 3.7 Test 2 results

The duration of Test 2 was three hours and 36 minutes. This test was done twice. At the first time it was not noticed that the thermal protection relay of the 250 A MCCB was set to a lower tripping setting. Approximately 30 minutes from the start of the test the outgoing breaker tripped. The trip setting of the thermal relay was set to 250 A level and the MCCB was closed again. The test was finished according to the test plan, but it was decided to repeat the test again.

At the second time, there was no tripping. In the thesis are presented the first time test of test 2 in wireless temperature graph (Figure 64 & Appendix 11) and the second time test of the test 2 in wired temperature graph (Figure 63 & Appendix 9). Final results of both of these tests are the same, the difference in the tests is only that the breaker tripped and was reset in the first time test.

Figure 61. Power cable L1, L2 and ambient normal image

Figure 62. Power cable L1, L2 and ambient IR image

62

Figure 63. Temperature rise graph of test 2 with wired sensors (second time test)

IntelliSAW software was recording data to an Excel file during the tests. One row of temperature data was recorded in every second. Total of 11723 rows of temperature data were created to the Excel file when test 2 was completed. Figure 64 is presenting a graph from the received Excel data. The results are also presented in attachments, Appendix 11.

Figure 64. Temperature rise graph of test 2 with IntelliSAW wireless sensors (first time test)

63 In Table 4 are presented the steady state temperature values of the two temperature monitoring systems at the end of test 2. The first column indicates the measurement location. The second and the third columns present the steady state values of the wired sensor system and the wireless IntelliSAW sensor system. The differences between the results of the wired and IntelliSAW monitoring systems are brought out in the “Difference” columns (differences brought out in temperature K values and in percentage).

Measurement place Wired

Table 4. Comparison of results of test 2

At the end of the measurements, thermal images at the sensor locations were taken. In figures 65 – 72 are presented the locations and the thermal images of each sensor location at the end of the test 2. From each measurement location normal and thermal images are presented.

Figure 65. Cable before MS L1, L2 and L3 normal image

Figure 66. Cable before MS L1, L2 and L3 IR image

64

Figure 68. Busbar (BB) connection after main-switch (MS) L1 IR image

Figure 72. Outgoing cable L1, L2 and L3 IR image

Figure 70. Vertical BB and cable connection L2 and L3 IR image

Figure 71. Outgoing cable L1, L2 and L3 normal image

Figure 69. Vertical BB and cable connection L2 and L3 normal image

Figure 67. Busbar (BB) connection after main-switch (MS) normal image

65 3.8 Conclusions

Two tests were performed in this thesis and temperatures were measured with three different temperature monitoring systems. The thermal imaging results are also added to the comparison tables with the difference analysis compared to the IntelliSAW system (Table 5 & Table 6).

Measurement place Wired

Busbar (BB) connection after main-switch (MS) L1 91.4/364.6 101.4/374.6 96.7/369.9 -10/-4.7 -3 %/1 %

BB connection after MS L2 - 103.1/376.3 95.1/368.3 -/8 -/2 %

BB connection after MS L3 95.1/368.3 98/371.2 90.2/363.4 -2.9/-7.8 -1 %/2 % Horizontal and vertical BB connection L1 63.3/336.5 62.2/335.4 64.1/337.3 1.1/1.9 0 %/1 % Horizontal and vertical BB connection L2 66.1/339.3 64.1/337.3 64.1/337.3 2.0/0.0 1 %/0 % Horizontal and vertical BB connection L3 60.8/334.0 63.9/337.1 63.9/337.1 -3.1/0.0 -1 %/0 %

Power cable L1 30.7/303.9 31.2/304.4 31.2/304.4 -0.5/0.0 0 %/0 %

Power cable L2 33.1/306.3 32/305.2 33.2/306.4 1.1/1.2 0 %/0 %

Ambient 20.3/293.5 22.6/295.8 22.8/296.0 -2.3/0.2 -1 %/0 %

Table 5. Comparison of results of test 1 including data from thermal camera

Measurement place Wired

Busbar (BB) connection after main-switch (MS) L1 38.3/311.5 42/315.2 42.1/315.3 -3.7/0.1 -1 %/0 % BB connection after MS L2 39.8/313.0 41.2/314.4 42.1/315.3 -1.4/0.9 0 %/0 % BB connection after MS L3 39.3/312.5 40/313.2 42.1/315.3 -0.7/2.1 0 %/1 % Vertical BB and cable connection L1 42.3/315.5 40.2/313.4 39.0/312.2 2.1/-1.2 1 %/0 % Vertical BB and cable connection L2 40.4/313.6 38.2/311.4 39.0/312.2 2.2/0.8 1 %/0 % Vertical BB and cable connection L3 35.3/308.5 38.4/311.6 38.2/311.4 -3.1/-0.2 -1 %/0 %

Outgoing cable L1 77.8/351.0 69.3/342.5 69.3/342.5 8.5/0.0 2 %/0 %

Outgoing cable L2 77.9/351.1 68.1/341.3 70.6/343.8 9.8/2.5 3 %/1 %

Outgoing cable L3 70.2/343.4 65.4/338.6 67.8/341.0 4.8/2.4 1 %/1 %

Ambient 21.7/294.9 22.6/295.8 22.8/296.0 -0.9/0.2 0 %/0 %

Table 6. Comparison of results of test 2 including data from thermal camera

66 The different temperature monitoring systems and devices have the following accuracies:

- IntelliSAW sensors = 2 degrees of celsius in the range of 0-80 degrees of celsius, 4 degrees of celsius in the full range (Intellisaw. 2016. IntelliSAW Sensor Installation Manual).

- Thermocouple Z2-K-5M = 1.5 degrees of celsius (Labfacility).

- Amplifiers AD8495 = 1 degrees of celsius (Analog devices. 2010).

- Fluke Ti400 = 2 degrees of celsius (Fluke. 2021).

In both tests, 12 connection points were monitored. Under temperatures of 80 celsius degrees, the error margin is 4 celsius degrees between the IntelliSAW system and the thermal camera.

Under temperatures of 80 celsius degrees, the error margin is 4.5 celsius degrees between the IntelliSAW system and the wired system (summarized accuracy 1 + 1.5). Over temperatures of 80 celsius degrees, error margin is 6 celsius degrees between the IntelliSAW system and the thermal camera. Over temperatures of 80 celsius degrees, the error margin is 6.5 celsius degrees between the IntelliSAW system and the wired system.

At test 1, over 80 celsius degrees the highest single temperature difference between the IntelliSAW system and the wired system is 10 celsius degrees. The highest single temperature difference between the IntelliSAW system and the thermal camera result is 8 celsius degrees.

At test 1, under 80 celsius degrees the highest single temperature difference between the IntelliSAW system and the wired system is 6.4 celsius degrees. The highest single temperature difference between the IntelliSAW system and the thermal camera result is 5 celsius degrees.

At test 2, under 80 celsius degrees the highest single temperature difference between the IntelliSAW system and the wired system is 9.8 celsius degrees. The highest single temperature difference between the IntelliSAW and the thermal camera result is 2.5 celsius degrees.

At test 1, there were in total 2 monitored connection points, where the result difference of the IntelliSAW system compared to results of both, the wired system and the thermal camera, were over error margin (of 4 – 4.5 celsius degrees). “Cable before MS L3” lesser difference was 5 celsius degrees and “BB connection after MS L2” difference was 8 celsius degrees.

67 At test 2, there were no monitored connection points, where the result difference of the IntelliSAW system compared to results of both, the wired system and the thermal camera, were over error margin (of 4 – 4.5 celsius degrees).

Manufacturers give the accuracies for the monitoring devices. There are still other factors, which will affect the accuracy, for example poor contact with the surface. Two different monitoring system results were compared with the IntelliSAW system result. The number of connection points of the IntelliSAW system, where both thermal camera and wired system results compared to the IntelliSAW results were over error margin, was two. “Cable before MS L3” value exceeded the error margin by 1 celsius degrees. “BB connection after MS L2”

exceeded the error margin by 4 celsius degrees. However, in that connection point the results

exceeded the error margin by 4 celsius degrees. However, in that connection point the results