4. DISTRIBUTION OF FAULT CURRENTS
4.4 Current distribution and reduction factor for underground cables
Similarly, as fault currents are distributed through shield wires, underground cables with metallic sheath or shield earthed at both ends can also act as current carrying conductors.
The reduction factor depends on the type of cable and is given by the cable manufacturer (IEC 60909-3 2009). According to the standard SFS 6001, the chain impedance of the cable sheath and neighboring earthing grids can be considered in addition to the reduction factor, but only if the cable is significantly longer than the sections forming the chain impedance.
If the substation has an outgoing cable, according to SFS 6001 the reduction factor of the cables is to be used in place of the shield wire reduction factor. IEC 60909-3 goes deeper into how reduction factors are calculated but as they are given in the standard or from the manufacturer, this calculation is not included in this thesis. For three single-core cables, the reduction factor can even be much lower than indicated, as all 3 sheaths can contribute to distribution of fault currents (Popovic 2003). The calculation of reduction factor r3 for three single-core cables is given in the formula (4.12). However, the reduction factor for one cable sheath is often enough, as the reduction factors for cables is even smaller than for overhead line shield wires.
In calculations, a distinction between a system with three single-core cables and a three-core cable connection must be made. As the outgoing cables from a substation are typically very large in diameter, the three single-core cable situation is the usual case and is considered below. The case of three-core cables is thoroughly presented in IEC 60909-3, but not pre-sented here due to relevancy and limitations. A distinction must also be made between two fault events, a line-to-earth short-circuit in station B with the short-circuit current fed from the station A, or a short-circuit between the stations A and B. These fault events with their respective fault current distributions are explained in the next subchapters.
4.4.1 Line-to-earth short circuit in station B
Figure 4.5 illustrates how the fault currents flow in the system in a case where the fault at station B is fed from station A.
Figure 4.5 Line-to-earth short circuit in station B with fault current fed from station A only.
(IEC 60909-3 2009)
In this fault case, the current through earth that flows back to station A can be calculated with the formula as also indicated in the figure
πΌπΈαΊπ΄ = π33πΌ(0)π΄ (4.11)
where r3 is the reduction factor for the three cables, that can be calculated by the formula (4.12) given in standard IEC 60909-3, where the layout and distances between cable phases are considered, or by using the reduction factors given in the standard SFS 6001. 3I(0)A can be assumed to be equal to Iβk1 in this case.
π3 = π β²π
π β²π+ 3 β ππ0
8 + π3 β π π0 2π ln
αΊ
βππππΏ1πΏ2ππΏ1πΏ3
3
(4.12)
The IEC 60909-3 standard gives detailed examples for calculating the reduction factors among other things. Therefore, the exact calculations and all formulas for variables are not presented.
4.4.2 Line-to-earth short circuit between stations A and B
Figure 4.6 illustrates how the fault currents flow in the system in a case where the fault occurs between two stations and is fed from both directions.
Figure 4.6 Line-to-earth short-circuit between stations with fault current fed from stations A and B, where
Iβk1 = 3I(0)A + 3I(0)B
3I(0)A = ISA + 3IEαΊA
3I(0)B = ISB + 3IEαΊB
(IEC 60909-3 2009)
Calculations of the current flowing through earth are considerably more complicated than in the simpler fault case presented in chapter 4.4.1. Two cases must be considered regarding earth potential rise, the current to earth at the short circuit location, and the currents through earth that flow to stations A and B.
The current to earth at the short circuit location is calculated as follows πΌπΈπΉ = π33πΌ(0)π΄ππΈππ‘ππ‘
π πΈπΉ + π33πΌ(0)π΅ππΈππ‘ππ‘
π πΈπΉ (4.13)
where REF is the resistance at the fault point against reference earth as shown in figure 4.6 and ZEStot is calculated as follows
ππΈππ‘ππ‘ = 1
1
πβ²πβπ΄+ 1
πβ²πβπ΅+ 1 π πΈπΉ
= πβ²πβπ΄βπ΅ β +πβ²πβπ΄βπ΅
π πΈπΉ
(4.14)
Equation is valid for cable lengths of at least β = αΊ/2, where αΊ is the equivalent earth pene-tration depth calculated with the following formula
αΊ = 1,851 60909-3, which are presented in table 4.2. (IEC 60909-3 2009)
Table 4.2 Equivalent earth penetration depths for different soil types. (IEC 60909-3 2009)
The currents flowing to the stations A and B are calculated as follows πΌπΈαΊπ΄ = π33πΌ(0)π΄ππΈππ‘ππ‘
ZβS is the self-impedance per unit length of one of the three sheaths or shields, which can be given as
RβS resistance per unit length of the sheath or shield (copper, aluminum, lead) RβS = 1/(ΞΊβ§qs) with qs β 2Οrsds where ds is the thickness of the sheath or shield rs is the medium radius of the sheath or shield
αΊ is the equivalent earth penetration depth presented above
Two further cases must then be considered regarding the fault point resistance as it is typi-cally unknown:
REF β β no connection at the short-circuit location between sheath/shield and the soil REF β min. connection between the cable sheath/shield and the soil
(IEC 60909-3 2009) 4.4.2.1 REF β β
In this case the resistance between the cable sheath or shield and the soil is infinite. It is assumed that the thermoplastic sheath is not destroyed by the fault current or by the arc at the fault location. In this case the equations for earth current are as follows
πΌπΈαΊπ΄ = π33πΌ(0)π΄βπ΄
Highest currents through the sheath or shield will occur if the fault location is close to station A or station B, and the short-circuit current is fed from both directions. Similarly, the highest currents through earth are found if the fault occurs near either station. (IEC 60909-3 2009) This can also be seen from the earth current formulas (4.18) above, which are as follows when the distance βA or βB is 0
πΌπΈαΊπ΄πππ₯ = βπ33πΌ(0)π΅ , (βπ΄ = 0) (4.19a)
πΌπΈαΊπ΅πππ₯ = βπ33πΌ(0)π΄ , (βπ΅ = 0) (4.19b)
where
r3 is the reduction factor for three single-core cables 3I(0)A (βA = 0) is the short-circuit current fed from the station A only 4.4.2.2 REF β min.
According to IEC 60909-3, a value of 5 β¦ can be used as a conservative estimate for the minimum resistance, as the connection to the surrounding earth is small. For determining the
currents through the earth, the formulas given above can be applied. As the determining current for earthing grid dimensioning is the highest current through the earth at the station, the prementioned formulas lead to
πΌπΈαΊπ΄πππ₯ = π33πΌ(0)π΄ , (βπ΄ = β) (4.20a)
πΌπΈαΊπ΅πππ₯ = π33πΌ(0)π΅ , (βπ΄ = 0) (4.20b)
If the current is fed from the station A only and the current fed from the other side is ne-glected for the worst-case scenario, the current 3I(0)A (βA = 0) is equal to Iβk1. The above design practices are valid for three single core cables regarding station earthing potential, and other practices must be followed when designing other systems with three-core cables.
More detailed formulas are available in the IEC 60909-3 standard, and only the most im-portant formulas considering this thesisβs subject area were presented.