ELEC-E8413 POWER SYSTEMS

EXAM 19.12.2016

1. Overcurrent protection of medium voltage distribution lines, including the relay settings.

2. Gas relay in transformer protection.

3. A transformer has the following name plate data: voltages 110/20 kV, rated power 25 MVA, no-load losses 21,8 kW, load losses 121 kW, short circuit impedance 10 %, magnetizing reactive power 0,45 %. Make the equivalent circuit of the transformer (at 20 kV level).

4. Explain different switching overvoltages when interrupting small inductive currents. What are the mitigation means against these overvoltages.

5. A 20 kV overhead line has positive sequence capacitance 10 nF/km and zero sequence capacitance of 4 nF/km. What is the phase-to-phase capacitance of the line per km?

6. The maximum heating of a conductor is 80 degrees, mass 145 kg/km, specific heat capacity 910 Ws/ oc kg and resistance 0,673 ohm/km. Compute the maximum 1 second short circuit

current.

Answer only in five questions!

Answers accepted in English, Finnish and Swedish.

Questions are available only in English.

Viittaukset

LIITTYVÄT TIEDOSTOT

This paper proposes an outer autonomous reactive power controller for active voltage level management in an example medium-voltage (MV) distribution network.. The developed new

The impact of doubling the primary distribution substation density on the annual total cost of the generic model neutral isolated distribution systems with different line reclosing

3.6 Thermal protection functions available in ABB protection relays ABB has two separate protection functions, thermal overload protection for motors (MPTTR) and

The trip signals from IEDs are sent back to the real time simulator by two different means; traditional digital signal and the IEC61850-8-1 GOOSE message.. The

Both of these methodologies are based on observing the time of arrival (ToA) of the original PD pulse arriving at the sensors, its subsequent reflected pulses arriving at the

Power system reconfiguration in a radial distribution network for reducing losses and to improve voltage profile using modified plant growth simulation algorithm with

Under a locked-rotor situation, voltage is applied to the stator winding, but rotor speed remains at zero speed. Typically, a locked-rotor situation happens when the applied start-

Resistance and reactance can be thought as parameters that affect how far the protection area reaches on the R- and X-axis. Fourth parameter, line angle, can be used to tilt